BoilerTool
Home / Greenstar 8000+ / 238
238

Boiler electronics faulty

Worcester Bosch Greenstar 8000+

Category
V
Remedy
1. Check the gas supply to the property and the inlet on the gas valve (check drop on inlet).
2. Check the connections on the gas valve and the board (loose connection).
3. Check the continuity down harness and replace if required.
4. Check the voltage to the gas valve (19–24 V DC approx. when demand).
5. Check for water on the gas valve connections.
6. Check the resistance on the gas valve (pins 1–2 approx. 69, 5 Ohms).
7. If all tests are correct: replace the PCB.
This code also applies to:
hello@boilertool.co.uk
© 2026 BoilerTool