Boiler electr. system fault
Remedy
No ionisation detected after ignition.
▶ Check the main shut-off valve, open if necessary.
▶ Check the appliance isolation valve, open if necessary.
▶ Measure the gas supply pressure at the rated heat input. If necessary, shut down the appliance and check the gas line.
▶ Check flame sense electrode and connecting lead, replace if required.
▶ Check venturi/injector for potential blockage.
▶ Measure the ionisation current.
▶ Check the protective earth conductor connection (PE) in the control unit.
▶ Check the ignition cable for damage, replace if necessary.
▶ Check functionality of gas valve and replace if necessary.
▶ Check CO2 settings at min and max output
▶ Check flue system.
▶ Check combustion air supply.
▶ Check the heat exchanger on the flue gas side for deposits, clean if necessary.