2966

Flow temperature rise in heat exchanger too rapid

Worcester Bosch Condens 7000 WP

Category
B
Remedy
1. Ensure that the heating circulation is working correctly.
2. Check pump setting, adjust to match heating system if necessary.
3. Connect the plug to the temperature sensor correctly.
4. Connect the plug to the control device correctly.
5. Attach the temperature sensor correctly.
6. Check the temperature sensor, replace if necessary.
7. Check temperature sensor connecting lead, replace if necessary.
This code also applies to: