No flame signal after ignition

Worcester Bosch Condens 7000 WP

Category
V
Remedy
1. Open the main shut-off valve.
2. Open the device shut-off valve.
3. Interrupt the power supply of the appliance and check the gas line.
4. Check the supply pressure of the gas line.
5. Check that the burner is working correctly, adjust burner if necessary.
6. Check CO2 content of combustion air, adjust if necessary.
7. Establish protective conductor connection (PE) in the control device.
8. Carry out function check for ignition.
9. Carry out function check for ionisation.
10.Connect the plug for the ionisation and ignition sections correctly.
11.Connect the plug for the air/gas ratio control valve correctly.
12.Check condensate pipes.
13. Check flue gas side of heat exchanger for pollution.
14.Check flame sense electrode, replace if necessary.
15.Check ignition electrode, replace if necessary.
16.Check ignition electrode connecting lead, replace if necessary.
17.Check flame sense electrode connecting lead, replace if necessary.
18.Check air/gas ratio control valve, replace if necessary.
19.Check control device/burner control unit, replace if necessary.